Product Introduction
With the development of society, people have higher and higher requirements for the safety and reliability of electricity. The high-voltage circuit breaker is responsible for the dual tasks of control and protection in the power system, and its performance is directly related to the safe operation of the power system. Mechanical characteristic parameter is one of the important parameters to judge circuit breaker performance. The circuit breaker analyzer manufactures provides convenience for dynamic analysis of various types of circuit breakers, and can accurately measure the mechanical dynamic characteristics of various voltage levels of high-voltage circuit breakers such as less oil, more oil, vacuum and sulfur hexafluoride. The high voltage circuit breaker analyzer supplier is responsible for the dual tasks of control and protection in the power system, and its performance is directly related to the safe operation of the power system. Mechanical characteristic parameter is one of the important parameters to judge circuit breaker performance.
Product functions
Circuit breaker mechanical characteristic testing
Comprehensively tests the mechanical operating performance of high-voltage circuit breakers, providing data support for equipment operating condition assessment.
Opening/closing time testing
Precisely measures the opening time, closing time, and operation time of each interrupter of the circuit breaker to determine whether operating performance is normal.
Interrupter synchronization testing
Detects the operation synchronization between multiple interrupters, promptly identifying non-synchronization issues during circuit breaker opening and closing.
Speed and travel testing
Measures the operating speed, contact travel, and displacement changes during circuit breaker opening and closing, analyzing the condition of the mechanical mechanism.
Closing resistor testing
Detects parameters related to the circuit breaker closing resistor, providing a basis for circuit breaker performance testing and fault analysis.
Test data and waveform analysis
Real-time display of test data and waveforms, with support for data storage, query, and on-site printing, facilitating analysis and recording of test results.
Technical parameters
Use environment | Input power supply | 220V±10% 50Hz±10% |
Atmospheric pressure | 86~106kpa | |
Temperature | -10~45℃ | |
Humidity | ≤ Q80%RH | |
Safety performance | Insulation resistance | >2MΩ |
Dielectric strength | Power supply on the chassis power frequency 1.5kV withstand voltage for 1 minute, no flashover and arcing | |
Basic parameters | time | Range:16000.0ms,Resolution:0.1ms error:①within 200ms,0.1ms±1 word ②200ms or above,±2% ③The same period,±0.1ms |
speed | Range:20.00m/s,Resolution0.01m/s error:①within 0~2m/s,±0.1m/s±1 digital ②2m/s or above,±0.2m/s | |
stroke | Vacuum circuit breaker:Range:50.0mm,Resolution:0.1mm,error:±0.5mm SF6 circuit breaker:Range:300.0mm,Resolution:0.1mm,error:±2mm Less oil circuit breaker:Range:600.0mm,Resolution:0.1mm,error:±2mm | |
Current | Range:20.00A ,Resolution:0.01A | |
Closing resistor | Range:0~2000Ω; Resolution:1Ω,Precision:1% | |
Fracture type | 12-way metal fracture, 6-way closing resistor fracture | |
Output power supply | DC30 ~ 250V digital adjustable / 20A (instantaneous work) | |
Dimensions | Host:360mm×290mm×280mm;annex:370mm×280mm×220mm | |
Weight | Host:6kg;annex:9kg |
Product Features
1.SF6 switch, GIS combination appliance, vacuum switch, oil switch for all model metal contacts produced at home and abroad.
2.Linear stroke sensor, rotary sensor, installation is very convenient, simple.
3.The host large screen, straight through, background LCD, contrast electronic adjustment. All Chinese menu prompt operation, switch action once, display all data and waveform map.
4.The host can store multiple sets of on-site points, closing test results, on-board real-time clock, easy to archive and save test date, time.
5.Bbuilt-in fast micro printer, print all data and maps.
6.Breaker Analyzer has powerful data analysis function, circuit breaker analyzer factory can effectively analyze various index parameters of circuit breaker mechanical characteristics.
Application Scenarios
Substation high-voltage circuit breaker testing
Used for on-site testing of mechanical characteristics such as opening/closing time, synchronization, speed, and travel of circuit breakers in substations.
Power equipment installation and commissioning
Suitable for installation, commissioning, and pre-commissioning performance testing of newly installed high-voltage circuit breakers.
Circuit breaker maintenance and servicing
Used for periodic equipment maintenance to assess the mechanical mechanism and contact operation status of circuit breakers.
Preventive testing of power equipment
Through testing key mechanical parameters of circuit breakers, promptly identifying potential faults and performance abnormalities.
GIS and high-voltage switchgear testing
Suitable for circuit breaker characteristic testing of GIS combined electrical apparatus, high-voltage switchgear, and other equipment.
Power equipment fault diagnosis
Analyzes circuit breaker abnormalities through test data and operation waveforms, providing a basis for fault location and repair.
FAQs:
Q: What is this device mainly used for testing?
A: It is mainly used for mechanical characteristic testing of high-voltage circuit breakers, including parameters such as opening/closing time, synchronization, operating speed, travel, and closing resistor.
Q: Can the analyzer test both opening and closing operations?
A:Yes. The instrument supports testing of both opening and closing operations of high-voltage circuit breakers. During the test, it records the corresponding operating time and mechanical characteristics and displays the results and waveforms for analysis. This allows technicians to evaluate the complete operating performance of the breaker rather than checking only a single operating action.
Q:Can the instrument measure the operating speed of a circuit breaker?
A:Yes. When equipped with the appropriate travel measurement sensor, the analyzer can measure the movement of the breaker mechanism and calculate its operating speed. Speed measurements can help technicians analyze the opening and closing movement of the contacts and identify changes in mechanical operating characteristics.