Product Introduction
Intelligent instrument calibrator for PT CT error and impedance admittance test.It meets the requirements of JJG313-94 current transformer verification regulation and JJG314-94 voltage transformer verification regulation.
Product Characteristics
1、Intelligent transformer calibrator adopts 320 240 lattice liquid crystal, with large visual range and long life backlight, convenient to use
2、Chinese operation interface, beautiful interface
3、The percentage difference Angle difference is displayed in large font, which is convenient for users to observe
4、The intelligent transformer calibrator produced by our company fully meets the requirements of jjg314-1993 and jjg314-1994, and it can be sampled automatically
5、Automatically judge polarity error, change ratio error
6、The upper computer software has the open function of virtual instrument
7、Completely solve the s-level measurement problem
8、Automatic range switching
9、The perfect combination of advanced and unique circuit and DSP technology can completely remove the problem of the circuit instability
10、power dissipation:<15VA(No micro printer);<25VA(microprinter)
11、Harmonic suppression ratio:>40db
12、boundary dimension(Band dimensions):260×350×150mm3
13、weight:6kg
Technical parameters
| Equipment operating environment | temperature:5℃~40℃ | relative humidity:<80%(25℃) |
| altitude:<2500m | ||
| mains frequency:50Hz±0.5Hz | mains input:220V±5V | |
| range of measurement | cophase component(%):0.0001~200.0 | distinguishability:0.0001 |
| orthogonal component(part):0.001~700.0 | distinguishability:0.001 | |
| impedance(Ω):0.0001~20.0 | distinguishability:0.0001 | |
| admittance(ms):0.0001~20.0 | distinguishability:0.0001 | |
| intrinsic error | cophase component | ΔX=±(X×2%+Y×2%)±Dx(Level 1 is optional) |
| orthogonal component | ΔY=±(X×2%+Y×2%)±Dy(Level 1 is optional) | |
| "X"、"Y"——Display value of instrument | ||
| "Dx,Dy"——Display value of instrument | ||
| Dx=2,Dy=5 | ||
| dial indicator | PETS2(Level 1 is optional) | |
| working range | electricity | (1%~149%)In (In =5A) |
| (5%~149%)In (In =1A) | ||
| voltage | (5%~149%)Un (Un =100V,150V,100V/) | |
| (5%~149%)Un (Un =100V/3) | ||
| workload | electricity | TO to TX<0.12Ω cosΦ=1 |
| voltage | a to x<0.25VA (100V) | |
| Polarity error indication | When the operating current (voltage) reaches more than 5% of the rated current (voltage) and the error exceeds 180%, there should be polarity indication. | |
| Note: if it is more than 10% of the rated operating current (voltage), there is still no proper polarity indication, indicating a fault. Please do not increase the current (voltage) to avoid burning out the instrument. | ||
| Variable ratio error indication | When the operating current (voltage) reaches more than 5% of the rated current (voltage) and the error exceeds 30% but is less than 180%, the error indication of variable ratio should be given. | |
| Insulation and voltage test and instructions | terminalTX( | |
| The power socket can withstand the housing1.5kV,1minwithstand voltage | ||